Honeywell Ignition Controls

With more than a decade of service in the field, the S8610U is time tested and proven. You can replace more than 300 competitive models with the S8610U and know that Honeywell’s long history of quality and reliable service is working for you.
Electrical Ratings

  • Voltage: 24V, 60 Hz

    • Current Draw: 1A pilot valve, 2A main valve
    • Valve Contact Rating: 0.2A

  • Trial For Ignition:

    • 15 second or 90 second field selected (pilot and main gas)

  • Ignition Sequence:

    • Continuous retry; after trial for ignition, pilot gas shuts off for 5 minutes before the next retry takes place

  • Maximum Valve Load @ 24 Vac (Amps):

    • 1A Pilot, 2A Main @ 165° F; 1A Pilot, 1A Main @ 175° F
  • Special Features:

    • Vent damper connection with automatic vent damper plug; makes for easy replacement for appliances with or without a vent damper

    • EnviraCOM communications for additional diagnostics
















S8610U3009 Spec Sheet
Honeywell Direct Spark Ignition Control Modules Spec
Item IDDescriptionPkg QtyUnit SizeQuantity
Q3400A1024
IGNITOR/FLAME ROD ASSY11
S8610U3009
HONEYWELL INGITION MODULE11
S87C1030
24V 2 ROD 21SEC DIRECT SPARK IGNITOR11
S87D1004
24V 2 ROD 6SEC DIRECT SPARK IGNITOR11
S87D1012
24V 2 ROD 11SEC DIRECT SPARK IGNITOR11
S8910U1000
24V 1/2 ROD 4/7SEC DIR HOT SURF IGNITION11